Protective system control FCU

The protective system control FCU 500 is designed for the monitoring and controlling of central safety functions in multiple burner systems on an industrial furnace.

Overview
  • For monitoring and controlling central safety functions in multiple burner systems on industrial furnaces
  • Checking of the valves and system for tightness using a valve proving system
  • Safe recording of the furnace chamber temperature on high temperature equipment by a temperature monitor or temperature limiter
  • Long service life due to replaceable power module for fail-safe outputs, can be programmed according to customer requirements
  • EU certified, FM and EAC approved, certified for systems up to SIL 3 (compliant with PL e), FCU..H0: CSA approved
More Information:
Specifications

Actuation, Valve & Motion Control Specifications

  • Actuator Type
    • IC20, IC40, RBW three‑point step, frequency converter fan control (via terminals 53-56)
  • Valve Type
    • V1, V2, V3, relief valve configuration options as per tightness test scenario (parameters 52-53)

Control, Safety & Functional Behavior

  • Timing Adjustments
    • tGV (fan run‑up), tPV (pre‑purge), tPN (post‑purge), tRF (enable delay), tMP (min pause), tE (switch‑on delay), tL1/tL2 (valve opening), tM (measurement time)

Temperature Control/Measurement

  • Temperature Monitoring
    • STM (≥750 deg C high temp mode), STL/FSTL (max furnace temp 200-1600 deg C), double thermocouple Types K, N, S only (H1 versions)

Standards & Certifications

  • Safety Level
    • SIL 3 (EN 61508), PL e (ISO 13849) Certified
  • Approvals
    • FM Approved, EU‑GAR 2016/426, EMC 2014/30/EU, LVD 2014/35/EU, ANSI/CSA Z21.20; Eurasian CU approval

Control, Software & User Interface Specifications

  • Program Sequences
    • Startup, Safety Interlock Checks, Pre‑Purge, Airflow Monitoring, Tightness Test, Ignition Enable, Operation, Post‑Purge

Overview

  • Product Type
    • Protective system control for monitoring and controlling central safety functions in multi‑burner furnace systems
  • Models
    • FCU 500 (central control), FCU 505 (zone control)

Electrical Specifications

  • Power Supply
    • 120 VAC (Q), 230 VAC (W); 24 VDC control voltage ±10%

Software, Configuration & Cyber

  • Parameter Storage
    • Replaceable parameter chip card; settings transferable across units with identical type code

Inputs, Outputs & Signal Interfaces

  • Outputs
    • AC/24VDC - Gas valves V1(13), V2(14), V3(15), LDS start limits (16), Purge (17), High Temp (18), Fault 24V (41), Operation 24V (42), Capacity control (53-56), Fan (58), Safety interlock (57)

Installation & Mounting Specifications

  • Installation Type
    • DIN‑rail mount 35 x 7.5 mm, control cabinet ≥IP54, no condensation allowed

Performance Specifications

  • Input Capacity
    • 24 VDC - Start (1), Controlled air flow (2), Remote reset (3), Burner operation (4), Fan ready (44), VPS/POC (45), Emergency stop (46), Air min (47), Air flow (48), Gas min (49), Gas max (50), Programmable inputs (51,65,66,67,68)

Environmental Conditions

  • Environmental Rating
    • Cabinet IP54; OCU faceplate IP65
    • Operating -20 to +60 deg C

Communication & Interfaces

  • Communication Options
    • PROFINET/Modbus TCP via BCM 500 module; cyclic and acyclic data (status, faults, remaining times, STM/STL temps)

Applications & Compatibility

  • Applications
    • Gas min./max., air min., pre‑purge, tightness test, temperature monitoring, burner start enable, zone capacity control

Actuation, Valve & Motion Control Specifications

  • Actuator Type
    • IC20, IC40, RBW three‑point step, frequency converter fan control (via terminals 53-56)
  • Valve Type
    • V1, V2, V3, relief valve configuration options as per tightness test scenario (parameters 52-53)

Control, Safety & Functional Behavior

  • Timing Adjustments
    • tGV (fan run‑up), tPV (pre‑purge), tPN (post‑purge), tRF (enable delay), tMP (min pause), tE (switch‑on delay), tL1/tL2 (valve opening), tM (measurement time)

Temperature Control/Measurement

  • Temperature Monitoring
    • STM (≥750 deg C high temp mode), STL/FSTL (max furnace temp 200-1600 deg C), double thermocouple Types K, N, S only (H1 versions)

Standards & Certifications

  • Safety Level
    • SIL 3 (EN 61508), PL e (ISO 13849) Certified
  • Approvals
    • FM Approved, EU‑GAR 2016/426, EMC 2014/30/EU, LVD 2014/35/EU, ANSI/CSA Z21.20; Eurasian CU approval

Control, Software & User Interface Specifications

  • Program Sequences
    • Startup, Safety Interlock Checks, Pre‑Purge, Airflow Monitoring, Tightness Test, Ignition Enable, Operation, Post‑Purge

Overview

  • Product Type
    • Protective system control for monitoring and controlling central safety functions in multi‑burner furnace systems
  • Models
    • FCU 500 (central control), FCU 505 (zone control)

Electrical Specifications

  • Power Supply
    • 120 VAC (Q), 230 VAC (W); 24 VDC control voltage ±10%

Software, Configuration & Cyber

  • Parameter Storage
    • Replaceable parameter chip card; settings transferable across units with identical type code

Inputs, Outputs & Signal Interfaces

  • Outputs
    • AC/24VDC - Gas valves V1(13), V2(14), V3(15), LDS start limits (16), Purge (17), High Temp (18), Fault 24V (41), Operation 24V (42), Capacity control (53-56), Fan (58), Safety interlock (57)

Installation & Mounting Specifications

  • Installation Type
    • DIN‑rail mount 35 x 7.5 mm, control cabinet ≥IP54, no condensation allowed

Performance Specifications

  • Input Capacity
    • 24 VDC - Start (1), Controlled air flow (2), Remote reset (3), Burner operation (4), Fan ready (44), VPS/POC (45), Emergency stop (46), Air min (47), Air flow (48), Gas min (49), Gas max (50), Programmable inputs (51,65,66,67,68)

Environmental Conditions

  • Environmental Rating
    • Cabinet IP54; OCU faceplate IP65
    • Operating -20 to +60 deg C

Communication & Interfaces

  • Communication Options
    • PROFINET/Modbus TCP via BCM 500 module; cyclic and acyclic data (status, faults, remaining times, STM/STL temps)

Applications & Compatibility

  • Applications
    • Gas min./max., air min., pre‑purge, tightness test, temperature monitoring, burner start enable, zone capacity control
  • Actuator Type : IC20, IC40, RBW three‑point step, frequency converter fan control (via terminals 53-56)
  • Valve Type : V1, V2, V3, relief valve configuration options as per tightness test scenario (parameters 52-53)
  • Timing Adjustments : tGV (fan run‑up), tPV (pre‑purge), tPN (post‑purge), tRF (enable delay), tMP (min pause), tE (switch‑on delay), tL1/tL2 (valve opening), tM (measurement time)
  • Temperature Monitoring : STM (≥750 deg C high temp mode), STL/FSTL (max furnace temp 200-1600 deg C), double thermocouple Types K, N, S only (H1 versions)
  • Safety Level : SIL 3 (EN 61508), PL e (ISO 13849) Certified
  • Program Sequences : Startup, Safety Interlock Checks, Pre‑Purge, Airflow Monitoring, Tightness Test, Ignition Enable, Operation, Post‑Purge
  • Product Type : Protective system control for monitoring and controlling central safety functions in multi‑burner furnace systems
  • Power Supply : 120 VAC (Q), 230 VAC (W); 24 VDC control voltage ±10%
  • Parameter Storage : Replaceable parameter chip card; settings transferable across units with identical type code
  • Outputs : AC/24VDC - Gas valves V1(13), V2(14), V3(15), LDS start limits (16), Purge (17), High Temp (18), Fault 24V (41), Operation 24V (42), Capacity control (53-56), Fan (58), Safety interlock (57)
  • Models : FCU 500 (central control), FCU 505 (zone control)
  • Installation Type : DIN‑rail mount 35 x 7.5 mm, control cabinet ≥IP54, no condensation allowed
  • Input Capacity : 24 VDC - Start (1), Controlled air flow (2), Remote reset (3), Burner operation (4), Fan ready (44), VPS/POC (45), Emergency stop (46), Air min (47), Air flow (48), Gas min (49), Gas max (50), Programmable inputs (51,65,66,67,68)
  • Environmental Rating : Cabinet IP54; OCU faceplate IP65|Operating -20 to +60 deg C
  • Communication Options : PROFINET/Modbus TCP via BCM 500 module; cyclic and acyclic data (status, faults, remaining times, STM/STL temps)
  • Approvals : FM Approved, EU‑GAR 2016/426, EMC 2014/30/EU, LVD 2014/35/EU, ANSI/CSA Z21.20; Eurasian CU approval
  • Applications : Gas min./max., air min., pre‑purge, tightness test, temperature monitoring, burner start enable, zone capacity control
Name
Description
File Size
Date
Size
No support documents tagged to this product
An error occurred . Please try after sometime
Category@category|Type@type

Filters

Product Number
Part Number
Description
Leaf Category
Thumbnail
Add to list
KS88621000
FCU500WC0F1H0K0-E
KS88621000
FCU500WC0F1H0K0-E
KS88621001
FCU500WC0F0H0K2-E
KS88621001
FCU500WC0F0H0K2-E
KS88621002
FCU500WC0F0H0K1-E
KS88621002
FCU500WC0F0H0K1-E
KS88621003
FCU500WC0F0H0K1-E
KS88621003
FCU500WC0F0H0K1-E
KS88621004
FCU500WC0F0H0K1-E
KS88621004
FCU500WC0F0H0K1-E
KS88621005
FCU500WC0F1H0K2-E
KS88621005
FCU500WC0F1H0K2-E
KS88621006
FCU500WC0F0H0K1-E
KS88621006
FCU500WC0F0H0K1-E
KS88621007
FCU500WC1F0H0K2-E
KS88621007
FCU500WC1F0H0K2-E
KS88621008
FCU500WC0F0H0K0-E
KS88621008
FCU500WC0F0H0K0-E
KS88621009
FCU500WC1F0H0K0-E
KS88621009
FCU500WC1F0H0K0-E